Approvals
Our MI Cable passes the UL2196 fire cable test the harshest and best possible way to test how durable a wiring system will be in fire.
This test and listing requires cables to be tested both horizontally in full scale 3 meter lengths with bends.
The fire temperature is 1850°F for a 2 hour exposure
The test voltage is 347/600 volts rms
The water spray is a high pressure firemens hose test.
Cables are required to be tested as a system with fixings and supports as they will be installed.
5 samples of each cable representing smallest to largest sizes are required to be tested in a horizontal mounting.
5 samples of each cable representing smallest to largest sizes are required to be tested in a vertical mounting.
Below is our full list of approvals
- UL2196 (Standard for Tests for Fire Resistive Cables)
- UL 514B (CONDUIT, TUBING, AND CABLE FITTINGS- Edition 6 – Revision Date 2014/11/21)
- 2 NO. 18.3-12 (CONDUIT, TUBING AND CABLE FITTINGS- Edition 2 – Revision Date 2014/11/21)
- UL 486A-486B (WIRE CONNECTORS- Edition 3 – Issue Date 2018/04/27)
- CSA C22.2 NO. 65-18 (WIRE CONNECTORS- Edition 6 – Issue Date 2018/04/27)
- UL504 (Outline of Investigation for Mineral-Insulated, Metal-Sheathed Cable)
NEC Fire Rated Applications:
The NEC recognizes critical electrical circuits that, in the event of a fire, must continue to perform their intended functions. NEC Article 695 and Article 700 address “Fire Pump” and “Emergency System” applications respectively.
Both require a minimum of a 2-hour fire-resistance rating which can be achieved through various methods. This requirement applies to the following:
- Fire Pump Feeders
- Emergency Generator Feeders
- Emergency Exhaust Fans
- Emergency Lighting
- Exit Signs
- Firemen’s Elevators
Office Address
26695 Eckel Road, Suite B, Perrysburg,
Ohio 43551
USA
[email protected]
Phone: 567-331-0101
Cell: (419) 575-7220